Wind Effects on Temperature Measurements

Wind significantly impacts infrared temperature readings. Moving air increases heat dissipation from the surface being measured through a process called convective cooling. This means that the temperature you measure with your infrared camera will be lower than the actual temperature of the component when there's no wind present.

To get an accurate understanding of how hot a component really is under normal (windless) conditions, you need to apply a correction factor. The stronger the wind, the more cooling occurs, and the larger the correction factor you'll need. Think of it like measuring someone's body temperature outside on a windy day versus in a calm room - the wind makes the surface cooler than it actually is internally. The correction factors in the table below help you calculate what the true excess temperature would be without wind interference.

Wind Compensation Calculator

Correct thermographic temperature readings based on ambient wind speed to determine actual component temperature.

Wind Speed Correction Factors (Metric)

Wind Speed (m/s) Correction Factor
0-1 m/s1.00
2 m/s1.36
3 m/s1.64
4 m/s1.86
5 m/s2.06
6 m/s2.23
7 m/s2.40
8 m/s2.50
9+ m/sNot Recommended

Beaufort Wind Scale (Metric)

Force Wind Speed (m/s) Classification Land Conditions
0< 0.5CalmSmoke rises vertically.
10.5 - 1.5Light AirDirection shown by smoke drift; vanes stay still.
21.6 - 3.3Light BreezeWind felt on face; leaves rustle; vanes move.
33.4 - 5.4Gentle BreezeLeaves & small twigs in constant motion; light flags extend.
45.5 - 7.9Moderate BreezeRaises dust and loose paper; small branches move.
58.0 - 10.7Fresh BreezeSmall trees in leaf begin to sway.
610.8 - 13.8Strong BreezeLarge branches in motion; umbrellas used with difficulty.
713.9 - 17.1Near GaleWhole trees in motion; resistance felt when walking.
817.2 - 20.7GaleTwigs break off trees; generally impedes progress.
920.8 - 24.4Strong GaleSlight structural damage; shingles may blow off.
Example: An excess temperature rise on a component is measured to be 5°C at a wind velocity of 8 m/s. The actual excess temperature is calculated to be 5 × 2.50 = 12.5°C.